Page 137 - Unistrut-Australia Catalog
P. 137

                                                                                  UNICLEATS - FAULT RATED CLEATS
  FAULT RATED CLEATS
   PERFORMANCE OF THE CABLE CLEATS
   Resistance to electromechanical force at 300mm spacing
  230ka at 300mm spacing
   Lateral load test
  Ave 25 kg
  Temperature range
 -40°c ~ 120°c
  Needle Flame test 650°c
 30 sec
  UV Resistance test
 1000hrs
  Cleat Material
 Composite
  Frame
 54mm* 2.0mm 316SS
  Nut & Bolt
 316SS
  Integral Pad
 Halogen Free
  Mounting Bolt
  Provided
      SINGLE CONDUCTOR SHORT CIRCUIT WITHSTAND TABLE
 Max Cable Cleat Spacing (A)
 Spacing Between Conductor Centres (mm)
 23
  25
 27
29
  31
 33
35
  37
 39
 41
43
  45
 47
49
  51
 53
 55
 57
 59
 61
   mm
  In
 IP peak (KA)
  225
8.8589
 179
  187
 194
203
  209
 216
220
  229
 234
 240
246
  250
 255
261
  266
 271
 276
 281
 286
 291
  300
11.81
 155
  163
 168
174
  181
 187
192
  198
 203
 209
214
  215
 220
225
  230
 235
 239
 244
 248
 252
  450
17.72
 128
  133
 137
144
  148
 152
157
  161
 165
 170
174
  178
 180
184
  189
 192
 195
 199
 202
 206
  600
23.62
 110
  115
 119
124
  128
 132
135
  139
 143
 148
150
  153
 156
160
  163
 166
 169
 172
 175
 178
  675
  900
 26.57
35.43
  104
 89
   108
  93
  113
 97
 117
102
   121
  105
  124
 108
 128
110
   132
  115
  135
 117
  139
 121
 143
124
   147
  127
  147
 128
 150
130
   154
  133
  156
 135
  159
 138
  162
 140
  165
 143
  168
 145
          www.unistrut.com.au 135
            FAULT RATED CABLE CLEATS
   C
T
E
U
R
L
T
E
S
B
4
F
2
9
1
R
O
S
I
N
A
C
E
S
R
T
A
E
Y
I
N
G
9
0
   135   136   137   138   139